品名 | SL-VGU1-EC |
---|---|
型號 | SL-VGU1-EC |
產品 | S-LINK V gateway controller for open network |
詳細 | For EtherCAT |
商品名稱 | 支援開放式網路S-LINK V閘道控制器 |
※為了商品改進,規格和外觀可能會在不事先通知的情況下變更,敬請諒解。
詳細規格
為了商品改進,規格和外觀可能會在不事先通知的情況下變更,敬請諒解。
項目 | 內容 |
---|---|
品名 | SL-VGU1-EC |
型號 | SL-VGU1-EC |
產品名 | S-LINK V gateway controller for open network |
Supply voltage | 24V DC+10-5% |
Current consumption | 300 mA or less (excluding error output load and power supply for driving I/O units) Note : The current consumption value shown here is the total of the maximum current (D-G line only) supplied to the S-LINK V I/O units and the current consumption of the S-LINK V gateway controller. |
Allowable through current | 7A Note : This product is not equipped with any short-circuit protective function. For this reason, select a power supply unit having short-circuit protective function (fuse, etc.). |
S-LINK V side : Transmission speed | A mode: 110 kbps, B mode: 27.5 kbps, C mode: 6.9 kbps |
S-LINK V side : Refresh time | A mode: 0.29 to 10.32 ms, B mode: 1.18 to 41.29 ms, C mode: 4.70 to 165.15 ms |
S-LINK V side : I/O points | Max. 512 points |
S-LINK V side : Connected node No. | Max. 256 nodes |
S-LINK V side : Transmission distance | A mode: 50 m 164 ft max., B mode: 200 m 656 ft max., C mode: 800 m 2,625 ft max. |
S-LINK V side : Total wiring length | A mode: 100 m 328 ft or less, B mode: 400 m 1,312 ft or less, C mode: 1,600 m 5,249 ft or less |
S-LINK V side : Transmission cable | Exclusive 4-core flat cable (0.5 mm2) or conductor cross-section area 0.3 to 2.0 mm2 4-core VCTF cable (without shield) Note : The VCTF cable is the vinyl cabtyre cable that conforms to the requirements of JIS C 3306 "Polyvinyl chloride insulated flexible cords." |
S-LINK V side : I/O combination | I/O settable in increments of 32 points |
S-LINK V side : Error output | NPN open-collector transistor |
EtherCAT communication side : Protocol | CoE PDO communication, SDO communication |
EtherCAT communication side : Compliance | IEEE802.3u (100BASE-TX) |
EtherCAT communication side : Transmission speed | 100 Mbps (100BASE-TX) |
EtherCAT communication side : Transmission connector | RJ-45 × 2 |
EtherCAT communication side : Distance between nodes | 100 m 328 ft or less |
EtherCAT communication side : Max. number of station connections | 4,095 stations (65,535 stations when set from master side) |
EtherCAT communication side : Transmission cable | Category 5e or more |
Ambient temperature | 0 to +55 ℃ +32 to +131 ℉ (No dew condensation), Storage: -20 to +70 ℃ -4 to +158 ℉ |
Ambient humidity | 10 to 90 % RH, Storage: 10 to 90 % RH |
Material | Enclosure: ABS |
Net weight | 140 g approx. |