品名 | SQ4-A22-N |
---|---|
型號 | SQ4-A22-N |
產品 | Safety Liquid Leak Sensor [Control Category 4 PLe SIL3] |
詳細 | Sensor [For chemical liquid] |
商品名稱 | 安全漏液感測器 [Type4 PLe SIL3] SQ4 |
※為了商品改進,規格和外觀可能會在不事先通知的情況下變更,敬請諒解。
詳細規格
為了商品改進,規格和外觀可能會在不事先通知的情況下變更,敬請諒解。
項目 | 內容 |
---|---|
品名 | SQ4-A22-N |
型號 | SQ4-A22-N |
產品名 | Safety Liquid Leak Sensor [Control Category 4 PLe SIL3] |
顯示價格 | Please contact our office |
Sensing object | Sulfuric acid, Hydrochloric acid,Phosphoric acid, Ammonia, Fluorinert (Note 2), Galden (Note 2), Hydrofl uoric acid etc. (Note 3) (Note 1) Highly viscous liquid may not be stably detected. (Note 2) The agents mentioned above are examples. It may not be detected depending on viscosity the agent.Before using this device, check the detecting liquid and installation condition. (Note 3) Fluorinert is the world wide trademark of 3M. Galden is the registered trademark of Solvay. |
Power voltage | 12 to 24 V DC plus or minus 10 % Ripple P-P 10 % or less |
Current consumption | 30 mA or less |
Utilization category | DC-12, DC-13 |
Detection output(Leakage detection) | NPN open-collector transistor - Maximum sink current: 50 mA - Applied voltage: Same as the supply voltage (between detection output and 0 V) - Residual voltage: 2 V or less (at 50 mA sink current) |
Detection output(Leakage detection):Response time | 10 ms or less |
Detection output(Leakage detection):Output operation | ON when normal condition or initial detection, OFF when detection leakage or wrong installation |
Detection output(Leakage detection):Short-circuit protection | Incorporated |
Detection auxiliary output(Initial detection) | NPN open-collector transistor - Maximum sink current: 50 mA - Applied voltage: Same as the supply voltage (between detection auxiliary output and 0 V) - Residual voltage: 2 V or less (at 50 mA sink current) |
Detection auxiliary output(Initial detection):Response time | 50 ms or less |
Detection auxiliary output(Initial detection):Output operation | ON when normal condition, OFF when initial detection or accidental leakage |
Detection auxiliary output(Initial detection):Short-circuit protection | Incorporated |
Protection | IP65 / IP67 (IEC) |
Ambient temperature | -10 to +55 ℃ +14 to +131 ℉ (No dew condensation or icing allowed) (Note) Storage: -10 to +55 ℃ +14 to +131 ℉ (Note) Liquid being detected should be also kept within the rated ambient temperature range. |
Ambient humidity | 35 to 85 % RH, Storage: 35 to 85 % RH |
Emitting element | Infrared LED (modulated) |
Material | Enclosure: PFA |
Cable | 0.1 mm2 4-core PFA cabtyre cable, 2 m 6.562 ft long |
Weight | Net weight: 45 g approx Gross weight: 110 g approx |