Mounting hole layout / minimum mounting center
Note: When using the safety lever lock, determine the vertical spacing(*1) in consideration of convenience for installing and removing the safety lever lock. (Recommended vertical spacing: 100 mm 3.937 in or more)
The 3.2+0.200.126+0.0080recess(*2) is for preventing rotation and not necessary when anti-rotation is not used.
- The minimum mounting centers are applicable to switches with one layer of contact blocks (two contact blocks).
When two layers of contact blocks are mounted, determine the minimum mounting centers in consideration of convenience for wiring.
Applicable wiring
(1) The applicable wire size is 2 mm2 maximum. (single wire ø1.6 mm ø0.063 in maximum) One or two wires can be connected.
・Applicable crimping terminal (Unit: mm in)
Be sure to use an insulation tube or cover on the crimping part of the crimping terminal to prevent electrical shocks.
・Single wire (Unit: mm in)
Note: When connecting wires to contact blocks or transformers in the direction [B], keep the insulation stripping length 6.6 mm 0.260 in at the maximum.
(2) Tighten the M3.5 terminal screws to a torque of 1.0 to 1.3 N・m.
Using the lever lock (accessory)
・Please attach the lever lock (yellow) after locking to prevent personnel from forgetting to lock the lock lever.