SF-CL1T264T|CC-Link Safety System Remote I/O Unit for Light Curtain SF-CL1T264T(Discontinued)
Download
Discontinued
Last time buy (JST)

*Photo may vary from actual product.
This product has been confirmed that it does not contain the 6 substances specified in EU RoHS Directive 2011/65/EU and the 4 substances specified in 2015/863/EU.
Spec Detail
Item | Specifications |
---|---|
Part Number | SF-CL1T264T |
Product Number | SF-CL1T264T |
Products Name | CC-Link Safety System Remote I/O Unit for Light Curtain |
The price of the product | Please contact our office |
Connectable safety light curtains | SF4B series |
Applicable standards | IEC 61508 SIL 3 |
Unit power:Supply voltage | 24 V DC plus or minus 10 % Ripple P-P 10 % or less (Note) The power supply connected to this product must satisfy the following conditions 1 SELV (Safety Extra Low Voltage): Reinforced insulated from hazardous potential part (48 V or more) 2 Compliance with the LVD (Low Voltage Directive) 3 Output voltage within 21.6 V to 26.4 V DC (Ripple P-P: 10 % or less.) |
Unit power:Current consumption | 140 mA or less (24 V DC, with all points ON) (Note) The power supply connected to this product must satisfy the following conditions 1 SELV (Safety Extra Low Voltage): Reinforced insulated from hazardous potential part (48 V or more) 2 Compliance with the LVD (Low Voltage Directive) 3 Output voltage within 21.6 V to 26.4 V DC (Ripple P-P: 10 % or less.) |
Unit power:Protective function | Unit power overvoltage / overcurrent protection function (Note) The power supply connected to this product must satisfy the following conditions 1 SELV (Safety Extra Low Voltage): Reinforced insulated from hazardous potential part (48 V or more) 2 Compliance with the LVD (Low Voltage Directive) 3 Output voltage within 21.6 V to 26.4 V DC (Ripple P-P: 10 % or less.) |
Unit power:Fuse | 0.8 A (Not replaceable) (Note) The power supply connected to this product must satisfy the following conditions 1 SELV (Safety Extra Low Voltage): Reinforced insulated from hazardous potential part (48 V or more) 2 Compliance with the LVD (Low Voltage Directive) 3 Output voltage within 21.6 V to 26.4 V DC (Ripple P-P: 10 % or less.) |
Unit power:Momentary power failure period | 10ms or less (Note) The power supply connected to this product must satisfy the following conditions 1 SELV (Safety Extra Low Voltage): Reinforced insulated from hazardous potential part (48 V or more) 2 Compliance with the LVD (Low Voltage Directive) 3 Output voltage within 21.6 V to 26.4 V DC (Ripple P-P: 10 % or less.) |
Input specifications:No. of input points | Input of light curtain: 2 points (with interference prevention function) Input of terminal block: 6 points (input terminals: 12 points) (Note) Total number of input points is 8 points, and use 2 points for control output (OSSD 1, 2) of 2 light cutains. Two inputs terminals are assigned for each input since dual wiring is supported. |
Input specifications:Insulation method | Photocoupler |
Input specifications:Rated input voltage | 24 V DC |
Input specifications:Rated input current | 4.6 mA approx. |
Input specifications:Operating voltage range | 24 V DC plus or minus 10 % Ripple P-P 10 % or less |
Input specifications:Max. simultaneous input points | 100% |
Input specifications:ON voltage / ON current | 15 V DC or more / 2 mA or more |
Input specifications:OFF voltage / OFF current | 5 V DC or less / 0.5 mA or less |
Input specifications:Input resistance | 5.6 kOhm approx. |
Input specifications:Input type | Negative common |
Input specifications:Response time | OFF to ON: 0.4 ms or less (at 24 V DC, excluding connecting device) ON to OFF: 0.4 ms or less (at 24 V DC, excluding connecting device) |
Input specifications:Safety remote station input response time | 32 ms or less + filter-out time (1 ms, 5 ms, 10 ms, 20 ms, 50 ms) |
dummy | 4 points (source + sink type) 2 points (source + source type) |
dummy | Photocoupler |
dummy | 24 V DC |
dummy | 24 V DC plus or minus 10 % Ripple P-P 10 % or less |
dummy | 0.5 A / point |
dummy | 1.0 A (10 ms or less) |
dummy | 0.5 mA or less |
dummy | 1.0 V DC or less |
dummy | Output short-circuit protection function |
dummy | Source + sink type, Source + source type |
dummy | OFF to ON: 0.4 ms or less (at 24 V DC) ON to OFF: 0.4 ms or less (at 24 V DC) |
dummy | 32 ms or less |
dummy | Incorporated (Zener diode) |
dummy | 24 V DC plus or minus 10 % Ripple P-P 10 % or less (Note) The power supply connected to this product must satisfy the following conditions 1 SELV (Safety Extra Low Voltage): Reinforced insulated from hazardous potential part (48 V or more) 2 Compliance with the LVD (Low Voltage Directive) 3 Output voltage within 21.6 V to 26.4 V DC (Ripple P-P: 10 % or less.) |
dummy | 60 mA (24 V DC, with all points ON, excluding external load current) (Note) The power supply connected to this product must satisfy the following conditions 1 SELV (Safety Extra Low Voltage): Reinforced insulated from hazardous potential part (48 V or more) 2 Compliance with the LVD (Low Voltage Directive) 3 Output voltage within 21.6 V to 26.4 V DC (Ripple P-P: 10 % or less.) |
dummy | External power supply overvoltage / overcurrent protection function (Note) The power supply connected to this product must satisfy the following conditions 1 SELV (Safety Extra Low Voltage): Reinforced insulated from hazardous potential part (48 V or more) 2 Compliance with the LVD (Low Voltage Directive) 3 Output voltage within 21.6 V to 26.4 V DC (Ripple P-P: 10 % or less.) |
dummy | 8 A (Not replaceable) (Note) The power supply connected to this product must satisfy the following conditions 1 SELV (Safety Extra Low Voltage): Reinforced insulated from hazardous potential part (48 V or more) 2 Compliance with the LVD (Low Voltage Directive) 3 Output voltage within 21.6 V to 26.4 V DC (Ripple P-P: 10 % or less.) |
dummy | 16 input points / common, 4 output points / common (Terminal block 2-wire type) |
dummy | Max. 4 A (Total of inputs and outputs) |
dummy | 1 station |
dummy | 10 12 times |
dummy | 38 ms |
Environmental resistance:Ambient temperature | 0 to +55 degrees +32 to +131 degrees Fahrenheit (No dew condensation), Storage: -40 to +75 degrees -40 to +167 degrees Fahrenheit |
Environmental resistance:Ambient humidity | 5 to 95 % RH, Storage: 5 to 95 % RH |
Environmental resistance:Voltage withstandability | 500V AC between all external DC terminals and ground, for 1 minute |
Environmental resistance:Insulation resistance | 10 MOhm or more between all external DC terminals and ground, by a 500 V DC insulation resistance tester |
Environmental resistance:Vibration resistance | Conforming to JIS B 3502, IEC 61131-2 |
Environmental resistance:Shock resistance | Conforming to JIS B 3502, IEC 61131-2 |
Overvoltage category | II |
Pollution degree | 2 |
Wiring cable | 0.3 to 2.0 mm2 |
dummy | RAV1.25-3 (Conforming to JIS B 2805) (Applicalbe wire size: 0.3 to 1.25 mm2) |
Weight | Net weight: 0.7 kg approx. |