EX-FC1|Leak Detection Sensor EX-F70/EX-F60
Download
*Photo may vary from actual product.
This product has been confirmed that it does not contain the 6 substances specified in EU RoHS Directive 2011/65/EU and the 4 substances specified in 2015/863/EU.
Product Number | EX-FC1 |
---|---|
Part Number | EX-FC1 |
Product | Simple wire-saving unit |
Product Name | Leak Detection Sensor EX-F70/EX-F60 |
*Specifications and design of the products are subject to change without notice for the product improvement.
Spec Detail
Specifications and design of the products are subject to change without notice for the product improvement.
Item | Specifications |
---|---|
Part Number | EX-FC1 |
Product Number | EX-FC1 |
Products Name | Simple wire-saving unit |
Applicable regulations and certifications | CE Marking (EMC Directive, RoHS Directive), UKCA Marking (EMC Regulations, RoHS Regulations), UL Recognition |
Applicable connector | SL-CP1 |
Supply voltage | 12 to 24 V DC ± 10 % Ripple P-P 10 % or less |
Current consumption | 50 mA or less (for the unit itself), 135 mA or less (including the sensor input current when all outputs of sensors are ON) |
Output | Relay contact 1a - Switching capacity: 30 V 1 A DC (resistive load) - Min. applied load: 10 mV 10 μA DC - Electrical lifetime: 100,000 switching operations or more (rated load, switching frequency 20 operations/min.) - Mechanical lifetime: 50 million switching operations or more (switching frequency 180 operations/min.) |
Output:Output operation | The output relay is ON when the input signal from the sensor is ON Note : Even with only one leak detection sensor connected, an OFF signal is output if the sensor detects liquid leakage, or if the unit has been installed incorrectly. |
Response time | 5 ms or less (excluding the response time of the sensor) |
Input No. | 8 Nos. [PNP output type sensors (leak detection sensors, general sensors) cannot be connected.] |
Indicators : Normal | Green LED x 8 (light up when the sensor is connected to each channel and the connection setting switch is set to ON) |
Indicators : Error | Red LED x 8 (light up when the leak liquid is detected by a sensor connected to each channel or a sensor is mounted improperly) |
Indicators : Output | Orange LED (lights up when the output relay is ON (normal)) |
Ambient temperature | -10 to +60 ℃ +14 to +140 ℉ (No dew condensation or icing allowed), Storage: -20 to +70 ℃ - 4 to +158 ℉ |
Ambient humidity | 35 to 85 % RH, Storage: 35 to 85 % RH |
Material | Enclosure: ABS, Unit mounting base: POM, Terminal part: PBT |
Cable | 0.2 mm2 4-core cabtyre cable, 2 m 6.562 ft long |
Cable extension | Extension up to total less than 10 m 32.808 ft is possible, with 0.3 mm2, or more, cable. |
Weight | Net weight: 85 g approx. |
Accessory | SL-CP1 (Snap male connector): 8 pcs., MS-SL-2 (Unit mounting base): 1 pc. |