EX-F61-PN|Leak Detection Sensor EX-F70/EX-F60
Download
*Photo may vary from actual product.
This product has been confirmed that it does not contain the 6 substances specified in EU RoHS Directive 2011/65/EU and the 4 substances specified in 2015/863/EU.
Product Number | EX-F61-PN |
---|---|
Part Number | EX-F61-PN |
Product | Leak Detection Sensor |
Details | Chemical-resistant |
Product Name | Leak Detection Sensor EX-F70/EX-F60 |
*Specifications and design of the products are subject to change without notice for the product improvement.
Spec Detail
Specifications and design of the products are subject to change without notice for the product improvement.
Item | Specifications |
---|---|
Part Number | EX-F61-PN |
Product Number | EX-F61-PN |
Products Name | Leak Detection Sensor |
Product details | Chemical-resistant |
Applicable regulations and certifications | CE Marking (EMC Directive, RoHS Directive), UKCA Marking (EMC Regulations, RoHS Regulations), UL Recognition |
Sensing object | Water, Agent, such as Sulfuric acid, Hydrochloric acid, Phosphoric acid or Ammonia etc. Note : Highly viscous liquid may not be detected stably. Note : The agents mentioned above are examples. For details, please contact our office. Note : PVC mounting bracket may not be used depending on type or viscosity etc. of the agent. For details, please contact our office. |
Supply voltage | 12 to 24 V DC ± 10 % Ripple P-P 10 % or less |
Current consumption | 15 mA or less |
Output | PNP open-collector transistor - Maximum source current: 50 mA - Applied voltage: 30 V DC or less (between output and +V) - Residual voltage: 1.0 V or less (at 50 mA source current), 0.4 V or less (at 16 mA source current) |
Output:Output operation | In normal state: ON, When leak detected or the sensor is mounted improperly: OFF |
Output:Short-circuit protection | Incorporated |
Response time | 50 ms or less |
FAULT indicator | Red LED (lights up when the leak liquid is detected, or the sensor is mounted improperly) |
NORMAL indicator | Green LED (lights up when the sensor is mounted properly) |
Protection | IP67 (IEC) |
Ambient temperature | -10 to +60 ℃ +14 to +140 ℉ (No dew condensation or icing allowed), Storage: -20 to +70 ℃ - 4 to +158 ℉ Note : Liquid being detected should also be kept within the rated ambient temperature range. |
Ambient humidity | 35 to 85 % RH, Storage: 35 to 85 % RH |
Ambient illuminance | Incandescent light: 1,000 ℓx or less at the light-receiving face |
Emitting element | Infrared LED (non-modulated) |
Material | Enclosure: PFA |
Cable extension | Extension up to total 50 m |
Weight | Net weight: 60 g approx. |
Accessory | MS-EX-F6-1(PFA mounting bracket): 1 pc. |