SC-GU3-01|Communication Unit for Open Network SC-GU3
Download
*Photo may vary from actual product.
This product has been confirmed that it does not contain the 6 substances specified in EU RoHS Directive 2011/65/EU and the 4 substances specified in 2015/863/EU.
Product Number | SC-GU3-01 |
---|---|
Part Number | SC-GU3-01 |
Product | Commnunication Unit for Open Network |
Details | Communication unit for CC-Link |
Product Name | Communication Unit for Open Network SC-GU3 |
*Specifications and design of the products are subject to change without notice for the product improvement.
Spec Detail
Specifications and design of the products are subject to change without notice for the product improvement.
Item | Specifications |
---|---|
Part Number | SC-GU3-01 |
Product Number | SC-GU3-01 |
Products Name | Commnunication Unit for Open Network |
Product details | Communication unit for CC-Link |
The price of the product | Please contact our office |
Applicable regulations | CE Marking (EMC Directive, RoHS Directive), UKCA Marking (EMC Regulations, RoHS Regulations) |
Compatible sensor units | Sensor amplifiers (NPN output type) that can connect to the SC‑71 cascading connector unit (optional) |
Number of units connectable | Maximum of 16 units can be connected to one SC-GU3-01 unit (Max. 12 units when FX-500 / LS-500 series is connected) |
Supply voltage | 24V DC +10/-15% Ripple P-P 10 % or less |
Current consumption | 120 mA or less (excluding connected sensor amplifiers) |
Allowable passing current | Wire-saving connector 2 A (Note 1), supply connector 6 A (Note 2) (Note 1) Be sure to check that total current consumption of sensor amplifiers connected in cascade does not exceed allowable passing current. (Note 2) In case of supplying power to other devices, be sure to set the current less than allowable passing current. |
Communication method | CC-Link Ver.1.10 |
Number of occupied station | Switchable 1 or 4 station |
Communication speed / Total extension length | 10Mbps / 100m 328.084 ft 5Mbps / 150m 492.126 ft 2.5Mbps / 200m 656.168 ft 625kbps / 600m 1968.504 ft 156kbps / 1,200m 3937.008 ft |
Communication cable | Specified cable (twist pair cable with shield) (Note) Use only a special-use communication cable that is approved by the CC-Link Partner Association. |
Station No. setting | 1 to 64 (0 and 65 or higher result in an error) |
Remote station type | Remote device station |
Ambient temperature | –10 to +55 ℃ +14 to +131 ℉ (No dew condensation or icing allowed), (If 4 to 7 units are connected in cascade: –10 to +50 ℃ +14 to +122 ℉, if 8 to 16 units are connected in cascade: –10 to +45 ℃ +14 to +113 ℉) Storage: –20 to +70 ℃ –4 to +158 ℉ |
Ambient humidity | 35 to 85 % RH, Storage: 35 to 85 % RH |
Material | Enclosure: Polycarbonate |
Weight | Net weight: 80 g approx. Gross weight: 120 g |