Adjustable range | 20 to 40 mm 0.787 to 1.575 in | 30 to 100 mm 1.181 to 3.937 in | 30 to 200 mm 1.181 to 7.874 in |
---|
Sensing range (with white non-glossy paper) | 0 to 40mm 0 to 1.575 in | 0 to 100mm 0 to 3.937 in | 0 to 200mm 0 to 7.874 in |
---|
Hysteresis | 5 % or less of operation distance | 20 % or less of operation distance |
---|
Repeatability (perpendicular to sensing axis) | Along sensing axis: 1 mm 0.039 in or less, Perpendicular to sensing axis: 0.2 mm 0.008 in or less (with white non-glossy paper) |
---|
Supply voltage | 12 to 24 V DC±10 % Ripple P-P 10 % or less |
---|
Current consumption | 45 mA or less (NPN output type), 50 mA or less (PNP output type) |
---|
Sensing output | <NPN output type> NPN open-collector transistor ・Maximum sink current: 100 mA ・Applied voltage: 30 V DC or less (between output and 0 V) ・Residual voltage: 1 V or less (at 100 mA sink current) 0.4 V or less (at 16 mA sink current)
<PNP output type> PNP open-collector transistor ・Maximum source current: 100 mA ・Applied voltage: 30 V DC or less (between output and +V) ・Residual voltage: 1 V or less (at 100 mA source current) 0.4 V or less (at 16 mA source current) |
---|
| Output operation | Switchable either Detection-ON or Detection-OFF |
---|
Response time | 1 ms or less |
---|
Distance adjuster | 2-turn adjuster with indicator |
---|
Protection | IP67 (IEC) |
---|
Ambient temperature | -20 to +55 ℃ +4 to -131 ℉ (No dew condensation or icing allowed) Storage: -25 to +70 ℃ -13 to +158℉ |
---|
Material | Enclosure: PBT, Lens: Polycarbonate Indicator cover: Polycarbonate |
---|
Cable | 0.2mm2 4-core oil, heat and cold resistant cabtyre cable, 2 m 6.562 ft long |
---|
Weight | 50 g approx. |
---|