FX-551L3-P-C2|Digital Fiber Sensor FX-550L
Download
*Photo may vary from actual product.
This product has been confirmed that it does not contain the 6 substances specified in EU RoHS Directive 2011/65/EU and the 4 substances specified in 2015/863/EU.
Product Number | FX-551L3-P-C2 |
---|---|
Part Number | FX-551L3-P-C2 |
Product Name | Digital Fiber Sensor FX-550L |
*Specifications and design of the products are subject to change without notice for the product improvement.
Spec Detail
Specifications and design of the products are subject to change without notice for the product improvement.
Item | Specifications |
---|---|
Part Number | FX-551L3-P-C2 |
Product Number | FX-551L3-P-C2 |
Applicable regulations | CE Marking (EMC Directive, RoHS Directive), UKCA Marking (EMC Regulations, RoHS Regulations) |
Supply voltage | 12 to 24 V DC +10-15% Ripple P-P 10 % or less |
Power consumption | Normal operation: 960 mW or less (current consumption 40 mA or less at 24 V supply voltage) ECO mode: 720 mW or less (current consumption 30 mA or less at 24 V supply voltage) |
Communication output (C/Q):IO-Link communication | IO-Link Specification V1.1 (Note:)When the sensor is used as an ordinary sensor, the communication output (C/Q) provides the same output operation as the control output (DO). |
Communication output (C/Q):Baud rate | COM3 (230.4 kbps) (Note:)When the sensor is used as an ordinary sensor, the communication output (C/Q) provides the same output operation as the control output (DO). |
Communication output (C/Q):Process data | 4 byte (Note:)When the sensor is used as an ordinary sensor, the communication output (C/Q) provides the same output operation as the control output (DO). |
Communication output (C/Q):Minimum cycle time | 1.0 ms (Note:)When the sensor is used as an ordinary sensor, the communication output (C/Q) provides the same output operation as the control output (DO). |
Control output (DO) | PNP open-collector transistor • Maximum source current: 50 mA • Applied voltage: 30 V DC or less (between output and +V) • Residual voltage: 2 V or less (Note) (at maximum source current) (Note:)In case of using the cable (cable length 2 m 6.562 ft). |
Control output (DO):Output operation | Switchable either Light-ON or Dark-ON by L/D mode |
Control output (DO):Short-circuit protection | Incorporated |
Response time | STD: 250 μs or less, LONG: 2 ms or less, U-LG: 4 ms or less, HYPR: 24 ms or less, selectable |
Sensitivity setting | 2-point teaching / Limit teaching / Full-auto teaching / Manual adjustment |
Incident light sensitivity setting | Incorporated, 4 steps |
Incident light intensity display range | STD: 0 to 4,000, LONG: 0 to 8,000, U-LG / HYPR: 0 to 9,999 |
Timer function | Incorporated with variable OFF-delay / ON-delay / One-shot, switchable either effective or ineffective |
Timer function:Timer period | 0.1 to 999.9 ms approx., in units of 0.1 ms approx. |
Different frequency interference prevention function | Incorporated (up to 4 units). Note that the response time varies depending on the setting. F-1: 0.8 ms or less, F-2: 0.9 ms or less, F-3: 1.0 ms or less, F-4: 1.7 ms or less (Note:)This function increases the hysteresis. Check the sensing condition when using the function. |
Protection | IP40 (IEC) |
Ambient temperature | -10 to +55℃ +14 to +131℉ (If 4 to 7 units are mounted in cascade: -10 to +50℃ +14 to +122℉ or if 8 to 16 units are mounted in cascade: -10 to +45℃ +14 to +113℉) (No dew condensation or icing allowed), Storage: -20 to +70℃ -4 to +158℉ |
Vibration resistance | 10 to 150 Hz frequency, 0.75 mm 0.030 in double amplitude (10 G max.) in X, Y and Z directions for two hours each |
Shock resistance | 98 m/s2 acceleration (10 G approx.) in X, Y and Z directions five times each |
Emitting element (modulated) | Red LED (Peak emission wavelength: 660 nm 0.026 mil) |
Material | Enclosure, Case cover: Polycarbonate, Switch: Polyacetal |
Cable | 0.2 mm2 4-core cabtyre cable, 2 m 6.562 ft long |
Cable extension | Extension up to total 20 m 65.617 ft is possible with 0.3 mm2, or more, cable. (Condition of CE compliance: less tan 20 m 65.617 ft) (however, supply voltage 12 V DC or more) |
Weight | Net weight: 55 g approx., Gross weight: 80 g approx. |
Remark | Where measurement conditions have not been specified precisely, the conditions used were an ambient temperature of +23℃ +73.4℉. |