Panasonic Industry / Automation Controls
Panasonic Industry / Automation Controls

KT4H/B Temperature Controllers (Discontinued Products)

  • Discontinued Products

  • Number System

  • Rating/ Performance

  • Dimensions

  • Wiring/ Connection

  • Cautions For Use

Ⅾiscontinued

Last time buy (JST)

September 29, 2023

We are sorry, the products have been discontinued. Please refer to the details of the discontinued products and the recommended substitutes list below.

------------------------------ Tab1 showing ------------------------------

Discontinued Products

------------------------------ Tab2 showing ------------------------------

Number System

KT4H series (Ash grey)

fig_KT4H

Notes:

1) CT1 or CT2 for current transformer is provided as an accessory when heater burnout alarm is added.
2) Under some conditions, option functions (shaded items) may not be available; please check the “Description” of the above table for non-functioning 
circumstances

Model No. search method 

Example: When the optional functions (heating/cooling: relay contact, communication function: serial communication) are added on to the basic function
• Model No.: AKT4H1111101

KT4B series (Black)

fig_KT4B

Notes:

1) Please inquire if you need specifications not included in the model numbers above. On our website, it is easy to find products by model number selection 
or by searching for specifications.
2) Use RS-485 for serial communication.

------------------------------ Tab3 showing ------------------------------

Rating/ Performance

Rating and Specifications

ItemSpecifications
CE marking directive complianceLow Voltage Directive, EMC Directive, RoHS Directive
Size (W×H×D)48×48 1.890×1.890 in
RatingSupply voltage (Must be specified)100 - 240V AC
24V AC/DC
Frequency50/60Hz
Rating power consumption8 VA approx.
Rated graduationInput typeInput range
ThermocoupleK-200 to 1,370℃(-320 to 2,500℉)
-200.0 to 400.0℃(-320.0 to 750.0℉)
J-200 to 1,000℃(-320 to 1,800℉)
R0 to 1,760℃(0 to 3,200℉)
S0 to 1,760℃(0 to 3,200℉)
B0 to 1,820℃(0 to 3,300℉)
E-200 to 800℃(-320 to 1,500℉)
T-200.0 to 400.0℃(-320.0 to 7,50.0℉)
N-200 to 1,300℃(-320 to 2,300℉)
PL-II0 to 1,390℃(0 to 2,500℉)
C(W/Re5-26)0 to 2,315℃(0 to 4,200℉)
RTDPt100-200 to 850℃ (-320 to 1500℉)
-200.0 to 850.0℃(-320.0 to 1500.0℉)
JPt100-200 to 500℃(-320 to 900℉)
-200.0 to 500.0℃(-320.0 to 900.0℉)
DCCurrent4 to 20mA DC-2,000 to 10,000
0 to 20mA DC
Voltage0 to 1V DC
0 to 10V DC
1 to 5V DC
0 to 5V DC
 · Scaling and change to the decimal point position is possible for DC current input and DC voltage input.
· DC current input is supported with an externally connected 50Ω shunt resistor (sold separately).
Sensor
input
ThermocoupleK, J, R, S, B, E, T, N, PL-II, C (W/Re5-26)
External resistor: Max. 100Ω (max. 40Ω external resistor for B input)
RTDPt100, JPt100 3-conductor system (Allowable input conductor resistance for each conductor: max. 10Ωor less)
DC current0 to 20mA DCInput impedance: 50Ω (Connect 50Ω shunt resistor between input terminals.)
Allowable input current: 50 mA or less (When 50Ω shunt resistor is used)
4 to 20mA DC
DC voltage0 to 1V DCInput impedance: 1 MΩ or more, Allowable input voltage: 5 V or less, Allowable signal source resistance: 2 kΩ or less
0 to 5V DCInput impedance: 100 kΩ or more, 1 to 5 V DC Allowable input voltage: 15 V or less, Allowable signal source resistance: 100 Ω or less
1 to 5V DC
0 to 10V DC
Control outputRelay contact(Must be specified)3 A 250 V AC (at resistive load), 1 A 250 V AC (at inductive load cos ø = 0.4), Electrical life: 100,000 times
Non-contact voltage
(Voltage output for SSR drive )
12+20 V DC, Max. load current: 40mA (with short circuit protection circuit)
DC current4 to 20mADC Load resistance: Max. 550Ω
Alarm output 1 (EV1)Relay contact 1a 3A 250V AC (Resistive load), 1a 1A 250V AC (cosø=0.4)
Electrical life: 100,000 times
Alarm output 2 (EVT2)Same as Alarm output 1
Control methodPID action (with auto-tuning function), PI action, PD action (with manual reset function), P action (with manual reset function), ON / OFF action
Target temperature settingPrimary setting / secondary setting / third setting / fourth setting (switched by external terminal)
Indication accuracyThermocoupleWithin ± (0.2 % + 1 digit) of each input span or within ±2℃ (4℉) whichever is greater However, R or S input; within ±6℃ (12℉) in the range of 0 to 200℃ (32 to 392℉) B input, range of 0 to 300℃ (32 to 572℉): accuracy is not guaranteed K, J, E, T, and N input, less than 0℃ (32℉): within ± (0.4 % ±1 digit) of input span
RTDWithin ±(0.1 % + 1 digit) of each input span or ±1℃ (2℉) whichever is greater
DC current and DC voltageWithin ±0.2% ±1 digit of each input span
Sampling period250ms
Hysteresis (ON/OFF)Thermocouple and RTD: 0.1 to 100.0℃()
DC current and DC voltage: 1 to 1,000 (The decimal point place follows the selection)
Proportional band0 to 1,000℃ (0 to 2,000℉)
Input with decimal point:
0.0 to 1,000.0℃ (0.0 to 1,000.0℉)
DC current and DC voltage: 0.0 to 100.0 %
Integral time0 to 1,000 seconds
Derivative time0 to 300 seconds
Proportional cycle1 to 120 seconds
Allowable voltage fluctuationWhen 100-240 V AC: 85-264 V AC, When 24 V AC/DC: 20-28 V AC/DC
Insulated resistance500 V DC, Min. 10 MΩ
Breakdown voltageBetween input terminal and power terminal
Between output terminal and power terminal
1.5 kV AC for 1 min.
Malfunction vibration10 to 55 Hz (1 cycle/min.), single amplitude: 0.35 mm 0.014 in (10 min. on 3 axes)
Breakdown vibration10 to 55 Hz (1 cycle/min.), single amplitude: 0.75 mm 0.030 in (1 hour on 3 axes)
Malfunction shockX, Y and Z each direction for 5 times 98 m/s2
Breakdown shockSame as above, but 294 m/s2
Ambient temperature0 to +50℃ 32 to +122℉
Ambient humidity35 to 85%RH (No condensation)
Mass120 g approx.
WaterproofIP66 (applicable only to the front panel subject to rubber gasket employed)
Display character heightPV: 12mm 0.472 in SV: 6mm 0.236 in
Option functionsHeating/ Cooling controlRelay contact1a Control capacity: 3 A 250 V AC (at resistive load), Electrical life: 100,000 times
Non-contact
voltage
12 V DC ±15 %, Max. 40 mA (with short circuit protection circuit)
Heater burnout alarm
output
For KT4H only: Specify either single phase 20 A, singlephase 50 A, 3 phases 20 A, or 3 phases50 A for rated heater current.
Setting accuracy: within ±5 % of rated heater current Relay contact 1a 3 A 250 V AC (at resistive load), Electrical life: 100,000 times
Communication functionPlease refer below to “Communication Function Overview”.
AccessoriesMounting frame / Mounting bracketIncluded with controller
Terminal coverSold separately
Included with controllerIncluded with controller

Communication Function Overview

Communication typeHalf-duplex
Communication speedSelect 2400, 4800, 9600, or 19200 bps using key operation.
Synchronization typeAsynchronous
ProtocolModbus RTU, Modbus ASCII, MEWTOCOL (Slave)
CodingBinary/ASCII
InterfaceEIA RS-485 compliant
No. of nodes31
Maximum cable length1,000 m 3,280.840 ft (cable resistance must be within 50Ω)

------------------------------ Tab4 showing ------------------------------

Dimensions

  • Unit: mm in

Panel cut-out dimensions

When installing in series

General tolerance : ±1.0±0.39Note:If longitudinal or lateral close mounting is used for the controller, IP66 specification (Dust-proof/Drip-proof) may be compromised, and all warranties will be invalidated.

CT1

Current transformer (CT) (for 5, 10, and 20A)

CT2

Current transformer (CT) (for 50 A)

Note:

Current transformer CT1 or CT2 is included (only with KT7 and KT4H)
when heater burnout alarm function is added.

AKT4H801

Terminal cover (for KT4H / KT4B / KT4R)

AKT4H801

AKW4822

Mounting frame (for KT4R / KT4H / KT4B)

AKW4822

AKT4H820

Tool cable(for KT4H / KT4B)

AKT4H820

AKT4810

Shunt resistor

------------------------------ Tab5 showing ------------------------------

Wiring/ Connection

External Connection Diagram

POWER SUPPLY : Power supply voltage

EVT1 : Alarm output 1

EVT2 : Alarm output 2 (optional) or heater burnout alarm output (optional)

OUT1 : Control output or heating output (optional)

OUT2 : Cooling output (optional)

TC : Thermocouple input

RTD : Resistance temperature detector input

DC : DC current input (DCA) or DC voltage input (DCV)
(For DC voltage input, + side connection terminal differs depending on the voltage. Also, for DC current input, connect shunt resistor between No. (10) and (12) terminals.)

T1 : Current transformer input 1 (optional: for single phase and three phases)

CT2 : Current transformer input 2 (optional: for three phases)

DI : Contact input (optional)

RS-485 : Serial communication RS-485 (optional)

Communication Function Connection Diagram(PLC Connection Diagram)

Notes: 1)Shield wireTo prevent current flow along shield sections, ground one end of the shield wire.(If both ends of the shield section are grounded, a closed circuit with the earth will form and electricity flowing through the shield wire will cause increased susceptibility to noise.)2)Terminating Resistors (Terminators)The KT4H / KT4B series has a built-in pull-up resistor or pull-down resistor.For this reason, do not connect the terminating resistor on the communication line.

------------------------------ Tab6 showing ------------------------------

Cautions For Use

Mounting

Please install vertically in order to satisfy the IP66 specification for dust and splash proofing.
The possible control panel plate thickness for installation is between 1 to 5 mm 0.039 to 0.197 in.

(1)Insert the unit from the front of the control panel.

(2)Push the mounting frame fully into contact with the paneland tighten the screws. (Screw tightening torque: 0.05 N·m to 0.06 N・m)

Part description

Note: Color selection is the same for each size.

(1)Action indicators (backlight: Orange) ℉℃ : Lights respectively when temperature unit/ is selected. T/R : Lights during serial communication (optional) TX output. AT : Flashes during auto-tuning or auto-reset. OUT1 : Lights when control output is ON or heating output (optional)
is ON.
For DC current output type, it flashes corresponding to the
manipulated variable in 0.25 second cycles. OUT2 : Lights when cooling output (optional) is ON. EVT1 : Lights when alarm output 1 is ON. EVT2 : Lights when alarm output 2 (optional) is ON or heater burnout
alarm output (optional) is ON. LOCK : Lights when lock 1, lock 2 or lock 3 is selected. (2)MEMO display : Indicates the set value memory number. (backlight: Green) (3)PV display : Indicates the process value (PV). (backlight: Red / Orange /
Green) (4)SV display : Indicates the set value (SV). (backlight: Green) (5)Mode key : Selects the setting mode and registers the set value. (6)OUT/OFF key : The control output ON / OFF or auto / manual control
function can be switched. (7)Increase key : Increases the numeric value. (8)Decrease key : Decreases the numeric value. (9)Tool connector : By connecting the dedicated cable, the following operations can be conducted from the external computer.
  • Reading and setting of SV, PID and various set values
  • Reading of PV and action status
  • Function change

Notes on site selection

This controller is intended to be used in the following environment (IEC 61010-1)

Mount the controller in a place with:

  • Overvoltage category II and Pollution degree 2
  • A minimum of dust, and an absence of corrosive gases
  • No flammable, explosive gases
  • Few mechanical vibrations or shocks
  • No exposure to direct sunlight, an ambient temperature of -10 to 55 ℃ 14 to 131 ℉ that does not change rapidly. (When installing inside a panel, make particular allowance for heat dissipation. Avoid installation in situations such as above equipment that generates heat.)
  • Locations in which temperature rapidly changes may cause condensation.
  • Locations or atmospheres in which benzine, thinners, alcohol, or other organic solvents are present, or in which ammonia, sodium hydroxide, or other strong alkaline substances may adhere.
  • Locations susceptible to direct impact or the transmission of vibrations, or where splashing with water is possible.
  • In the proximity of equipment in which large switching surges occur or near high-voltage cables, high-voltage equipment, power lines, power equipment, ham radio transmitters, or equipment containing these or similar devices.
  • An ambient non-condensing humidity of 35 to 85 % RH
  • No large capacity electromagnetic switches or cables through which large current is flowing
  • No water, oil or chemicals or where the vapors of these substances can come into direct contact with the controller

Notes on wiring

Wire-pressed
terminal
Company nameType nameFastening
torque
Fork typeNICHIFU Co., Ltd.1.25Y-30.6 N•m
Max. 1.0 N•m.
J.S.T. Mfg. Co., Ltd.VD1.25-B3A
Round typeNICHIFU Co., Ltd.1.25-3
J.S.T. Mfg. Co., Ltd.V1.25-3
  • The terminal block of KT4R / KT8R / KT9R / KT4H / KT4B series are designed to be wired from the left side (The terminal of KT2 series are designed to be wired from the upper and lower direction). The lead wire must be inserted from the left side of the terminal, and fastened by the terminal screw. Use a wirepressed terminal with insulation sleeve that fits to the M3 screw.

  • Terminal screw fastening torque is 0.6 N·m to 1.0 N·m (for KT4R / KT8R / KT9R / KT4H / KT4B series). For KT7 series by M3 screw is less than 0.5 N·m and by M2 screw is less than 0.25 N·m respectively.
  • Use a thermocouple and compensating lead wire according to the sensor input specification of the controller.
  • Use a 3-wire system of RTD according to the sensor input specification of the controller.
  • This controller has no built-in power switch, circuit breaker and fuse. Therefore, it is necessary to install them in the circuit near the external controller. (Recommended fuse: Time-lag fuse, rating voltage 250 V AC, rating current 2 A)
  • In the case of 24 V AC / DC power supply, do not confuse the polarity when it is DC.
  • With the relay contact output type, use the relay externally according to the capacity of the load to protect the built-in relay contact.
  • When wiring, keep input wire (Thermocouple, RTD, etc.) away from power source wire and load wire.
  • Turn the power supply to the instrument off before wiring or checking. Working or touching the terminal with the power switched on may result in electric shock which could cause severe injury or death.
  • Do not drop wire chips into the holes of vent when wiring.
  • To prevent the controller from harmful effects of unexpected high level noise, it is recommended that a surge absorber be installed between the electromagnetic switch coils.

Notes on mounting

  • Do not use excessive force while screwing in the mounting frame and mounting bracket of KT4R / KT8R / KT9R / KT4H / KT4B series.
    For KT8R / KT9R series, recommended torque is approximately 0.1 N·m.
    For KT4H / KT4B series, recommended torque is approximately 0.05 to 0.06 N·m.
    For KT4R series, recommended torque is approximately 0.15 N·m.
  • When mounting the KT7 series to the DIN rail, mount it in a lateral direction. Make sure a click is audible when fixed into place.

Optional heater burnout alarm output
(for KT7 / KT4H series)

  • This alarm output is not available for detecting heater current under phase control.
  • Use the current transformer (CT) provided, and pass one lead wire of the heater circuit into the hole of CT.
  • When wiring, keep CT wire away from power source wire and load wire to avoid external interference.
  • In three phase installations for KT4H series, ensure that R, S and T are each connected to a 2-line CT that connects with CT1 [(13) - (14)] and CT2 [(14) - (15)] terminals.