AFPXHC14R|FP-XH
Download
*Photo may vary from actual product.
This product has been confirmed that it does not contain the 6 substances specified in EU RoHS Directive 2011/65/EU and the 4 substances specified in 2015/863/EU.
Product Number | AFPXHC14R |
---|---|
Part Number | AFPXHC14R |
Product | FP-XH Control Unit |
Details | C14 |
Product Name | FP-XH |
*Specifications and design of the products are subject to change without notice for the product improvement.
Spec Detail
Specifications and design of the products are subject to change without notice for the product improvement.
Item | Specifications |
---|---|
Part Number | AFPXHC14R |
Product Number | AFPXHC14R |
Products Name | FP-XH Control Unit |
Product details | C14 Power supply : 100 to 240V AC 8-point input of 24 V DC, 6-point relay output of 2 A |
General specifications
Item | Specifications |
---|---|
Operating temperature | 0 to +55 ℃ +32 to +131 ℉ |
Storage ambient temperature | -40 to +70 ℃ -40 to +158 ℉ |
Operating humidity | 10 to 95 % RH (at +25 ℃ +77 ℉, non-condensing) |
Storage ambient humidity | 10 to 95 % RH (at +25 ℃ +77 ℉, non-condensing) |
Breakdown voltage : Relay output | AC power supply Between power supply terminal and earth terminal : 1,500 V AC for 1 minute Between power supply terminal and service power supply terminal : 1,500 V AC for 1 minute Between input terminal and earth terminal : 1,500 V AC for 1 minute Between output terminal and earth terminal : 1,500 V AC for 1 minute (Note) : Cut-off current 5 mA (Initial value at shipment) |
Insulation resistance (Test voltage: 500 V DC) | Between power supply terminal and earth terminal : 100 MΩ or more (500 V DC using an insulation resistance meter) Between power supply terminal and service power supply terminal : 100 MΩ or more (500 V DC using an insulation resistance meter) Between input terminal and earth terminal : 100 MΩ or more (500 V DC using an insulation resistance meter) Between output terminal and earth terminal : 100 MΩ or more (500 V DC using an insulation resistance meter) |
Vibration resistance | 5 to 8.4 Hz, 3.5 mm 0.138 in single amplitude 8.4 to 150 Hz, Acceleration 9.8 m/s2 10 min. each in the X, Y and Z directions (1 octave/min) |
Shock resistance | 147 m/s2, 4 times each in the X, Y and Z directions |
Noise resistance | 1,000 V [P-P] with pulse widths of 50 ns and 1 μs (using a noise simulator) (Power supply terminal) |
Operating condition | No corrosive gas and no excessive dust |
Applicable standard for EC directives | EMC directive: EN 61131-2 (directive concerning emission, immunity and low voltage) |
Overvoltage class | Category II |
Level of contamination | 2 |
Functional specifications
Item | Specifications |
---|---|
Programming method | Relay symbol |
Control method | Cyclic operation |
Program memory | Built-in Flash ROM |
Program capacity | 16 k steps |
Basic instructions | Approx. 110 |
High-level instructions | Approx. 220 |
Operation speed | [Basic instruction (ST)] Approx. 0.04 μs/step (under 7 k steps) Approx. 0.7 μs/step (7 k steps or more) [High-level instruction (F0MV)] Approx. 0.22 μs/step (under 7 k steps) Approx. 1.73 μs/step (7 k steps or more) |
Operation memory : Link relay : External input (X) | 1,760 points (X0 to X109F) (Note) : The number of points in the table is the number of points of operation memory. The number of points actually available to be used is determined by the hardware configuration. |
Operation memory : Link relay : External output (Y) | 1,760 points (Y0 to Y109F) (Note) : The number of points in the table is the number of points of operation memory. The number of points actually available to be used is determined by the hardware configuration. |
Operation memory : Link relay : Internal relay (R) | Default: 8,192 points (R0 to R511F) FP-X compatible specifications: 4,096 points (Note) : Can be selected by the setting of the system register No. 1 (internal relay capacity). To provide compatibility with the conventional FP-X series control unit, select 4,096 points. |
Operation memory : Link relay : Special internal relay (R) | 240 points |
Operation memory : Link relay : Timer / Counter (T / C) | 1,024 points (Initial settings Timer: 1,008 points, Counter: 16 points) (Note) : The number of timer points can be changed by the setting of the system register No.5. |
Operation memory : Link relay : Link relay (L) | 2,048 points (L0 to L127F) |
Operation memory : Memory area : Data register (DT) | 12 k words |
Operation memory : Memory area : Special data register (DT) | 500 words |
Operation memory : Memory area : Link data register (LD) | 256 words (LD0 to LD255) |
Operation memory : Memory area : Index register (I) | 14 words (I0 to ID) |
Differential points | Points for program capacity |
Master control relay points (MCR) | 256 points |
Number of labels (JMP + LOOP) | 256 points |
Number of step ladders | 1,000 steps |
Number of subroutines | 500 subroutines |
High-speed counter : Control unit input | Single-phase 8 channels (10 kHz × 8) or 2-phase 4 channels (10 kHz × 4) (Note 1) : The maximum counting speed and maximum output frequency for the high-speed counter, pulse output and PWM output indicate the specifications for the voltage of 24 V DC and ambient temperature of +25 ℃ +77 ℉. The frequency may decrease depending on voltage, temperature or combination of functions used. (Note 2) : The inputs and outputs used for each function of the high-speed counter, pulse output, PWM output, pulse catch input or interrupt input cannot be allocated in duplication. |
High-speed counter : Pulse I/O with cassette installed | Single-phase 2 channels (100 kHz × 2) or 2-phase 1 channel (50 kHz × 1) (Note 1) : The maximum counting speed and maximum output frequency for the high-speed counter, pulse output and PWM output indicate the specifications for the voltage of 24 V DC and ambient temperature of +25 ℃ +77 ℉. The frequency may decrease depending on voltage, temperature or combination of functions used. (Note 2) : The inputs and outputs used for each function of the high-speed counter, pulse output, PWM output, pulse catch input or interrupt input cannot be allocated in duplication. |
Pulse output / PWM output : Pulse I/O with cassette installed | 1 channel [Pulse output] each 100 kHz [PWM output] 1 channel 1 Hz to 70 kHz (Resolution of 1000) 70.001 kHz to 100 kHz (Resolution of 100) (Note 1) : The maximum counting speed and maximum output frequency for the high-speed counter, pulse output and PWM output indicate the specifications for the voltage of 24 V DC and ambient temperature of +25 ℃ +77 ℉. The frequency may decrease depending on voltage, temperature or combination of functions used. (Note 2) : The inputs and outputs used for each function of the high-speed counter, pulse output, PWM output, pulse catch input or interrupt input cannot be allocated in duplication. |
Pulse catch input Interrupt input | 14 points (Control unit input: 8 points, Pulse I/O cassette : 3 points × 2) (Note) : The inputs and outputs used for each function of the high-speed counter, pulse output, PWM output, pulse catch input or interrupt input cannot be allocated in duplication. |
Periodical interrupt | 0.1 ms to 30 sec. (Note) : The inputs and outputs used for each function of the high-speed counter, pulse output, PWM output, pulse catch input or interrupt input cannot be allocated in duplication. |
Potentiometer input | 1 channel (0 to 4,000) |
Input time constant processing | Available |
Clock / calendar | Available (only when the master memory cassette AFPX-MRTC and battery are installed) |
Flash ROM backup : Backup by F12 / P13 instructions | All area of Data register |
Flash ROM backup : Automatic backup when power is off | Counter: 16 points, Internal relay: 128 points, Data register: 315 words |
Battery backup | Memory set in hold area of system register (only when battery is installed) |
Battery lifetime | 5 years or more in the actual use condition (operating 8 hours a day) (Note) : Battery lifetime values is calculated when the power is not completely turned on. Since the actual value depends on conditions of use, in practice, the lifetime may be shorter. |
Password | Yes (Can be selected from 4 digits, 8 digits or 32 digits) |
PLC link function | Max. 16 units, link relay: 1,024 points, link register: 128 words (Data transfer, remote programming: Not available) |