Panasonic Industry / Automation Controls
Panasonic Industry / Automation Controls

Data Logger Light (DLL) (Discontinued Products)

  • Discontinued Products

  • Specifications

  • Dimensions

Ⅾiscontinued

Last time buy

September 29, 2023

We are sorry, the products have been discontinued. Please refer to the details of the discontinued products and the recommended substitutes list below.

------------------------------ Tab1 showing ------------------------------

Discontinued Products

------------------------------ Tab2 showing ------------------------------

Specifications

General specifications

ItemDescription
Rated operating voltage100 to 240V AC
Allowable operating voltage range85 to 264V AC (85 to 110 % of rated operating voltage)
Rated frequency50 / 60Hz
Allowable momentary power-off timeMax.10ms
Rated output voltage24V DC
Output voltage range21.6V to 26.4V DC
Rated output current0.2A*1
Ambient temperature-10 to +55°C   +14 to +131°F
Storage temperature-25 to +70°C   -13 to +158°F
Current consumptionMax. 230 mA (at 100 V AC)
Weight200 g approx. (Excluding battery)

*1  If a current load over the specified level is continuously applied, the unit may break down. When a short circuit is detected, the whole power supply of Data Logger Light will be shut down.

Function specifications

ItemDescription
Data AccumulationLogged
Data
DescriptionInstantaneous, difference, average, minimum, and maximum values
Data format
(Valid for the register system)
16-bit integers (signed/unsigned),
32-bit integers (signed/unsigned),
64-bit integers (signed/unsigned),
HEX (4-digits/8-digits), Real number
Number of registrable files16
Number of registrable devices*1300 points/1 file
Data
stored
Stored to*2
  • Internal memory (SRAM) : 1 MB
  • SD/SDHC memory cards : 2 to 32 GB
File systemVFAT / FAT / FAT32
Stored formatCSV file type
Number of storable files100
TriggerTrigger type
  • Constant cycle (user-selectable from 1 second to 24 hours)
  • Contact status (rising edge, falling edge, both edges, accumulation ON time, number of accumulation open/close operations, ON status, and OFF status)
  • Specified time (every minute, every hour, every day, every week, every month, every year, and specified time)
  • Register (=, >, <, ≠)
  • Trigger combinations (AND, OR)
Number of registrable128
E-mail sending functionTransmission networkLAN
E-mail contentTitle: Within 16 one-byte or 8 two-byte characters
Body: Within 256 one-byte or 128 two-byte characters
Number of registrable64 (with no files attached)
Network functionCommunication protocolTCP/IP, UDP/IP
Application protocolSMTP (Capable of POP/APOP authentication),
FTP (client/server), SNTP, DHCP, DNS

*1  The maximum total number of points for registrable devices is always 300, for 16 files.

*2  The internal memory can store data using the backup battery.
Please note that data stored in the internal memory may be lost when the battery has been depleted.

Communication specifications

<Ethernet>

ItemDescription
InterfaceIEEE802.3U, 10BASE-T / 100BASE-TX
Connector typeRJ45
Transmission
specifications
Transmission speed10Mbps / 100Mbps
Transmission methodBase band
Max. segment length100m 328ft
Communication cableUTP (category 5)
FunctionsAuto-negotiation function,
MDI/MDI-X auto-crossover function

* Ethernet is a registered trademark of Fuji Xerox Co., Ltd. and Xerox Corporation.

<RS232C and RS485>

ItemDescription
InterfaceRS-232C (Not isolated
from the internal circuit)
RS-485 (Isolated
from the internal circuit)
Communication style1:1 communication1:N communication
Number of connected units1 unit99 units*1 *2
Communication methodHalf-duplex
Synchronous systemSynchronous communication method
Transmission distance15m 49 ftMax. 1200m 3,937 ft*3
Transmission speed4,800 / 9,600 / 19,200 / 38,400 / 57,600 / 115,200 bps
Transmission
format
Stop bit1-bits / 2-bits
ParityOdd / Even / None
Data length7-bits / 8-bits*4
ProtocolMEWTOCOL / Modbus RTU

*1  When using a PC as a slave station, you are recommended to use SI-35 or SI-35USB of LINEEYE Co., Ltd. as an RS485 interface.

*2  When using SI-35, SI-35USB, our Eco-POWER METER or our PLC (which can be connected up to 99 units), up to 99 units can be connected. In case using this system with other devices, up to 31 units can be connected.

*3  The transmission distance is limited by the transmission speed and the number of units connected. When the speed is 38,400 bps or lower, the maximum transmission distance is 1,200 m 3,937 ft, and the number of units is 99.

*4  With Modbus RTU protocol, it works only with 8-bit.

External memory specifications

<SD memory card slot>

ItemDescription
Support media*1SD / SDHC memory card
Supported format standards*2SD / SDHC standard conformance
Capacity2 to 32 GB
Speed classClass2 to Class10

*1  Please use the SLC type SD memory card.

*2  The use of UPS (Uninterruptible Power Supply) is recommended because data damage may occur in case of instant power failure during writing.

*3  Refer to the user manual regarding SD memory card handling.

------------------------------ Tab3 showing ------------------------------

Dimensions

  • Unit: mm in

Tolerance: ±1.0 ±0.04

MENU

Recently checked products

Recently checked product numbers