AFPRP2X08D2E|FP7 PHLS (Remote I/O) unit
Download
*Photo may vary from actual product.
This product has been confirmed that it does not contain the 6 substances specified in EU RoHS Directive 2011/65/EU and the 4 substances specified in 2015/863/EU.
Product Number | AFPRP2X08D2E |
---|---|
Part Number | AFPRP2X08D2E |
Product | FP7 PHLS (Remote I/O) unit |
Details | PHLS Slave units |
Product Name | FP7 PHLS (Remote I/O) unit |
*Specifications and design of the products are subject to change without notice for the product improvement.
Spec Detail
Specifications and design of the products are subject to change without notice for the product improvement.
Item | Specifications |
---|---|
Part Number | AFPRP2X08D2E |
Product Number | AFPRP2X08D2E |
Products Name | FP7 PHLS (Remote I/O) unit |
Product details | PHLS Slave units |
The price of the product | Please contact our office |
COMMUNICATION SPECIFICATIONS (Common)
Item | Specifications |
---|---|
Communication method | Two-wire system half duplex |
Insulation method | Pulse transformer insulation |
Communication speed | 6 Mbps / 12 Mbps |
Synchronous method | Bit synchronization |
Error check | CRC-12 |
Communication distance | Total length 200 m 656 ft (at 6 Mbps) / 100 m 328 ft (at 12 Mbps) (Note) Performance when the recommended cable is used Use of the recommended cable is necessary to achieve the maximum transmission distance and number of slave units. |
Connection method | Multi-drop method |
Impedance | 100 Ohm |
Terminator | Mounted on unit |
External interface | Connector-type terminal block |
INPUT SIDE SPECIFICATIONS
Item | Specifications |
---|---|
Insulation method | Non-isolated |
Rated input voltage | 24 V DC |
Rated input current | 4.3 mA approx. |
Input impedance | 5.6 kOhm approx. |
Min. ON voltage / Min. ON current | 17 V / 2 mA |
Max. OFF voltage / Max. OFF current | 5 V / 0.5 mA |
Response time:OFF→ON | 1 ms or less |
Response time:ON→OFF | 1 ms or less |
OUTPUT SIDE SPECIFICATIONS (Except relay)
Item | Specifications |
---|---|
Insulation method | Non-isolated |
Output type | Sink type (Open collector output) |
Rated load voltage | 20.4 to 28.8 V DC |
Max. control capacity | 0.1 A/point |
Max. surge current | 0.5 A |
OFF state leakage current | 0.1 mA or less |
ON state maximum voltage drop | 0.5 V or less |
Response time:OFF→ON | 0.05 ms or less |
Response time:ON→OFF | 0.5 ms or less |
Surge absorber | Zener diode |
Short circuit protection | None |
COMMON GENERAL SPECIFICATIONS
Item | Specifications |
---|---|
Ambient temperature | 0 to +55 ℃ +32 to +131 ℉, Storage: -40 to +70 ℃ -40 to +158 ℉ |
Ambient humidity | 10 to 95 % RH (at +25 ℃ +77 ℉, no condensation), Storage: 10 to 95 % RH (at +25 ℃ +77 ℉, no condensation) |
Vibration resistance | 5 to 8.4 Hz, single amplitude of 3.5 mm 0.138 in, 1 sweep/min. (IEC 61131-2) ; 8.4 to 150 Hz, constant acceleration of 9.8 m/s2, 1 sweep/min. (IEC 61131-2), 10 times each in X, Y, and Z directions |
Shock resistance | 147 m/s2 or more , 3 times each in X, Y, and Z directions (IEC61131-2) |
Noise immunity | 1,000 V [p-p] with pulse width 50 ns and 1 micro s (using a noise simulator) |
Operating condition | Free from corrosive gasses and excessive dust |
INDIVIDUAL GENERAL SPECIFICATIONS
Item | Specifications |
---|---|
Rated voltage range | 20.4 to 28.8 V DC |
Current consumption | 100 mA or less |
Net weight | 75 g approx. |