AFP7MXY32DWD|Multi input/output unit
Download
*Photo may vary from actual product.
This product has been confirmed that it does not contain the 6 substances specified in EU RoHS Directive 2011/65/EU and the 4 substances specified in 2015/863/EU.
Product Number | AFP7MXY32DWD |
---|---|
Part Number | AFP7MXY32DWD |
Product | FP7 Multi Input/Output Units |
Product Name | Multi input/output unit |
*Specifications and design of the products are subject to change without notice for the product improvement.
Spec Detail
Specifications and design of the products are subject to change without notice for the product improvement.
Item | Specifications |
---|---|
Part Number | AFP7MXY32DWD |
Product Number | AFP7MXY32DWD |
Products Name | FP7 Multi Input/Output Units |
Function specifications
Item | Specifications |
---|---|
Basic input and output : Number of occupied I/O points | Input/Output: 64 points each (4 words) |
Basic input and output : Number of external I/O points | Input: 16 points, Output: 16 points |
Basic input and output : Input time constant setting | None, 0.5 μs, 1 μs, 2 μs, 4 μs, 8 μs, 16 μs, 32 μs, 64 μs, 96 μs, 128 μs, 256 μs, 2 ms, 4 ms, 8 ms Setting possible in 2-point units |
Basic input and output : Output polarity setting | No output, N channel, P channel, Both channels (push pull output), Differential output Setting possible in 4-point units |
Interrupt : Number of points | 8 points/unit (Max. of 8 units can be used with FP7 system.) |
Interrupt : Mode | Non-interrupt unit, Interrupt unit (Set using DIP switches) |
Interrupt : Interrupt condition setting | Terminal input, Comparison match |
Counter : Counter type | Ring counter Linear counter |
Counter : Input mode | Direction distinction, Individual input, Phase input |
Counter : Number of channels | 4 channels (Note) : When using elapsed value hold function, number of channels will be limited. |
Counter : Counting range | Signed 32 bit (-2,147,483,648 to +2,174,483,647) Setting possible of upper and lower limits |
Counter : Max. counting speed | 5 V input voltage: 500 kHz 12 V input voltage: 500 kHz (350 kHz with phase input) 24 V input voltage: 250 kHz (180 kHz with phase input) (Note) With 50 % duty input pulse. |
Counter : Min. input pulse width | 0.5 μs |
Counter : Comparison output setting | Max. 8 points Terminal input counter: 4 channels |
Counter : Others | Transfer multiplication function (x 1, x 2, x 4) Elapsed value offset / preset function Elapsed value hold function, setting of upper / lower count limits Input pulse frequency measurement Overflow / underflow detection |
Pulse output : Number of channels | 4 channels |
Pulse output : Output mode | Direction distinction, Individual output, Phase output, Comparison match stop |
Pulse output : Output terminals : Pulse output function | 2 terminals / channel (B11 to B18 terminals) |
Pulse output : Output terminals : PWM output function | 1 terminal / channel (B11, B13, B15 and B17 terminals) |
Pulse output : Output frequency : Pulse output function | 1 to 500 kHz (Settable by 1 Hz) (Note) : When push pull setting or output current is 0.1 A. Varies according to load. |
Pulse output : Output frequency : PWM output function | 1 to 100 kHz (Settable by 1 Hz) (Note) : When push pull setting or output current is 0.1 A. Varies according to load. |
Pulse output : Duty ratio : Pulse output function | 50 % approx. (Fixed) |
Pulse output : Duty ratio : PWM output function | 0 to 100 % (Settable by 0.1%) |
Pulse output : Other functions | Pulse number measurement function (dedicated pulse counter 4 channels) |
COMMON GENERAL SPECIFICATIONS
Item | Specifications |
---|---|
Ambient temperature | 0 to +55 ℃ +32 to +131 ℉, Storage: -40 to +70 ℃ -40 to +158 ℉ |
Ambient humidity | 10 to 95 % RH (at +25 ℃ +77 ℉, no condensation), Storage: 10 to 95 % RH (at +25 ℃ +77 ℉, no condensation) |
Vibration resistance | 5 to 8.4 Hz, single amplitude of 3.5 mm 0.138 in, 1 sweep/min. (IEC 61131-2) ; 8.4 to 150 Hz, constant acceleration of 9.8 m/s2, 1 sweep/min. (IEC 61131-2), 10 times each in X, Y, and Z directions |
Shock resistance | 147 m/s2 or more , 3 times each in X, Y, and Z directions (IEC61131-2) |
Noise immunity | 1,000 V [p-p] with pulse width 50 ns and 1 μs (using a noise simulator) |
Operating condition | Free from corrosive gasses and excessive dust |
INDIVIDUAL GENERAL SPECIFICATIONS
Item | Specifications |
---|---|
Rated voltage range | - |
Current consumption | 100 mA or less |
Net weight | 100 g approx. |