Rating | Rated operating voltage | 24 to 240V AC/DC |
---|
Rated frequency | 50/60Hz common |
---|
Rated power consumption | 2.6 VA (AC), 1.4 W (DC) |
---|
Rated control capacity | 5A 250V AC (resistive load) |
---|
Operating mode | Pulse ON-delay Pulse Flicker Pulse ON-Flicker Signal OFF-delay Pulse One-shot Pulse One-cycle | Power ON-delay | Pulse ON-delay Pulse Flicker Pulse ON-flicker Signal OFF-delay Pulse One-shot Pulse One-cycle (with instantaneous contact) |
---|
Time range | 1s to 500h (Max.) 16 time ranges switchable |
---|
Time accuracy (Note) | Operating time fluctuation | ±0.3% (power off time change at the range of 0.1s to 1h) |
---|
Setting error | ±10% (Full-scale value) |
---|
Voltage error | ±0.5% (at the operating voltage changes between 85 to 110%) |
---|
Temperature error | ±2% (at 20℃ ambient temp. at the range of –10 to +55℃ +14 to +131℉) |
---|
Contact | Contact arrangement | Timed-out 2 Form C | Timed-out 1 Form C Instantaneous 1 Form C |
---|
Contact resistance (Initial value) | Max. 100mΩ (at 1A 6V DC) |
---|
Contact material | Silver alloy | Au flash on Silver alloy |
---|
Life | Mechanical (contact) | 2 x 107 | 1 x 107 |
---|
Electrical (contact) | 105 (at rated control capacity) |
---|
Electrical function | Allowable operating voltage range | 85 to 110% of rated operating voltage (at 20℃ coil temp.) |
---|
Insulation resistance (Initial value) | Min. 100MΩ (Between live and dead metal parts, Between input and output, Between contacts of different poles, Between contacts of same pole) (At 500V DC) |
---|
Breakdown voltage (Initial value) | 2,000Vrms for 1 min Between live and dead metal parts 2,000Vrms for 1 min Between input and output 2,000Vrms for 1 min Between contacts of different poles 1,000Vrms for 1 min Between contacts of same pole |
---|
Min. power off time | 100ms |
---|
Max. temperature rise | 55℃ 131℉ | 65℃ 149℉ |
---|
Mechanical function | Shock resistance | Functional | Min. 98m/s2 (4 times on 3 axes) |
---|
Destructive | Min. 980m/s2 (5 times on 3 axes) |
---|
Vibration resistance | Functional | 10 to 55Hz: 1 cycle/min Single amplitude of 0.35mm (10min on 3 axes) |
---|
Destructive | 10 to 55Hz: 1 cycle/min Single amplitude of 0.75mm (1h on 3 axes) |
---|
Operating condition | Ambient temperature | –10 to +55℃ +14 to +131℉ |
---|
Ambient humidity | Max. 85%RH (non-condensing) |
---|
Atmospheric pressure | 860 to 1,060hPa |
---|
Ripple factor (DC) | 20% |
---|
Others | Protective construction | IP40 |
---|
Weight | 120g 4.233 oz |
---|