Product Number | AFP7CCRM1 |
---|---|
Part Number | AFP7CCRM1 |
Product | FP7 Add-on Cassettes |
Details | Communication Cassettes |
Product Name | FP7 Add-on cassettes |
*Specifications and design of the products are subject to change without notice for the product improvement.
Spec Detail
Specifications and design of the products are subject to change without notice for the product improvement.
Item | Specifications |
---|---|
Part Number | AFP7CCRM1 |
Product Number | AFP7CCRM1 |
Products Name | FP7 Add-on Cassettes |
Product details | Communication Cassettes |
SPECIFICATIONS
Item | Specifications |
---|---|
Interface | RS-422 / RS-485 1 channel |
Transmission distance | Max. 1,200 m 3,937 ft at RS-485 mode, Max. 400 m 1,312 ft at RS-422 mode (Note) If mixed C-NET adapters are used, up to 32 units can be connected, but transmission speed will be limited to a maximum of 19.2 kbits/sec. |
Transmission speed | 300,600,1200,2400,4800,9600,19200,38400,57600,115200, 230400 bits/sec. |
Communication method | Half-duplex system |
Synchronous method | Start-stop synchronization system |
Transmission format | Stop bit: 1 bit / 2 bits Parity: Invalid / Valid (Odd / Even) Data length: 7 bits / 8 bits Start code: with STX / without STX End code: CR / CR + LF / None / ETX |
Data transmission order | Transmit from bit 0 in character units. |
Number of connected units | For general-purpose communication: Max. 99 units For computer link: Max. 99 units For PLC link: Max. 16 units For MODBUS-RTU: Max. 99 units (Note) If mixed C-NET adapters are used, up to 32 units can be connected, but transmission speed will be limited to a maximum of 19.2 kbits/sec. (Note) The converter SI-35 manufactured by LINE EYE Co., Ltd. is recommendable for the RS-485 at the computer side. When you use the SI-35, please adjust time after FP7 series PLC receives a command until it returns a response by a program. (Note) 1: 1 for RS-422 interface. |
COMMON GENERAL SPECIFICATIONS
Item | Specifications |
---|---|
Ambient temperature | 0 to +55 ℃ +32 to +131 ℉, Storage: -40 to +70 ℃ -40 to +158 ℉ |
Ambient humidity | 10 to 95 % RH (at +25 ℃ +77 ℉, no condensation), Storage: 10 to 95 % RH (at +25 ℃ +77 ℉, no condensation) |
Vibration resistance | 5 to 8.4 Hz, single amplitude of 3.5 mm 0.138 in, 1 sweep/min. (IEC 61131-2) ; 8.4 to 150 Hz, constant acceleration of 9.8 m/s2, 1 sweep/min. (IEC 61131-2), 10 times each in X, Y, and Z directions |
Shock resistance | 147 m/s2 or more , 3 times each in X, Y, and Z directions (IEC61131-2) |
Noise immunity | 1,000 V [p-p] with pulse width 50 ns and 1 micro s (using a noise simulator) |
Operating condition | Free from corrosive gasses and excessive dust |
INDIVIDUAL GENERAL SPECIFICATIONS
Item | Specifications |
---|---|
Rated voltage range | - |
Current consumption | 60 mA or less (Note) Increased CPU unit current consumption |
Net weight | 25 g approx. (with terminal block) |